This guide explains how inverter ratings work, how to estimate motor starting demand, how soft starters and variable speed drives change the picture, and how to check that a trailer will carry a site’s motor loads before it is deployed.
Three ratings on every inverter
Inverter data sheets usually show three figures. The continuous rating is what the unit can supply indefinitely at a stated ambient temperature. The overload rating, often somewhere around 120 to 150 percent, can be held for seconds to minutes. The surge or peak rating, which may be higher still, lasts only fractions of a second.
Motor starting falls between the surge and overload windows, because a direct-on-line motor takes from under a second to several seconds to reach speed depending on what it drives. Check how long each rating can actually be held, not just its headline value.
How much current a motor draws when it starts
A standard induction motor started direct-on-line typically draws five to seven times its full load current until it nears full speed, at a poor power factor. The starting kVA can therefore be many times the motor’s kW rating.
Loads that start against pressure, such as compressors and some pumps, take longer to accelerate and keep the high current flowing for longer. Fans and centrifugal pumps starting against an open valve accelerate more easily.
A worked example
Take a 1.5 kW single-phase pump motor at 230 V with a full load current of about 10 A. At six times full load current, the starting draw is about 60 A, or nearly 14 kVA for a moment. A trailer with a 5 kVA inverter and a short surge rating near 10 kVA would very likely trip on every start, even though the pump runs comfortably at 2 kVA once it is up to speed.
The same pump fitted with a variable speed drive or a suitable soft starter might start with well under twice its running current, which the same inverter could supply. Our article on solar trailers for pumping and dewatering shows how this applies to typical site pumps.
Soft starters and variable speed drives
A soft starter reduces voltage at start and ramps it up, lowering inrush current at the cost of reduced starting torque. It suits fans and lightly loaded pumps but may struggle with loads that need full torque from standstill.
A variable speed drive ramps both frequency and voltage, so the motor accelerates with current close to its running value. Drives also let operators run pumps at reduced speed to match demand, saving battery energy. Their downside is harmonic current, which the inverter must be able to tolerate, so check compatibility with the inverter maker.
The battery side of a surge
Every kilowatt the inverter delivers comes from the battery. A 10 kW draw on a 48 V battery bank means more than 200 A of DC current once inverter losses are included. The battery management system sets peak and continuous discharge limits, and if a surge exceeds them the BMS may disconnect the battery even if the inverter could cope.
DC cables, fuses and busbars must also carry these peaks without excessive voltage drop. A low battery state of charge or cold cells lowers available current further. Our guide to solar trailer battery sizing and chemistry explains how chemistry affects peak discharge.
Single phase or three phase
Many smaller trailers supply single-phase power only. Three-phase motors then need a drive that accepts single-phase input, or a trailer with a three-phase inverter. On three-phase trailers, check how much surge each phase can supply, since some designs share the overload capacity unevenly.
Unbalanced loads on a three-phase trailer reduce usable capacity. Spread single-phase loads across phases and keep a simple load schedule on the trailer door.
Power factor and real-world loads
Inverters are rated in kVA as well as kW. Motors, older fluorescent lighting and some chargers draw reactive current, which uses inverter capacity without delivering useful power. A load list in kW alone can hide an overloaded inverter.
Common site loads that cause trouble include air compressors, submersible pumps, refrigeration units, concrete vibrators and large power tools. Electronics such as cameras, LED lighting and routers rarely do.
Sequencing starts and adding generator assist
When several motors share one trailer, a simple controller or timer that prevents simultaneous starts often solves nuisance tripping. Starting the largest motor first, while other loads are off, gives it the full surge capacity.
Where a load needs more starting power than the inverter can ever supply, a hybrid trailer with a small generator that assists during starts and recharges the battery can be the practical answer. Our hybrid power systems cover these combinations.
Prove it before deployment
The safest approach is to test the actual load on the actual trailer before sending it to site. Record starting current, inverter alarms and battery voltage dip during several starts, including with the battery partly discharged.
If tests are not possible, ask for motor nameplate data, starter type and duty cycle, and size the inverter and battery with margin. A trailer that trips every morning costs far more in lost work than a larger inverter.
About the authors
This guide comes from the USP&E hybrid power engineers who specify and test solar trailers and small hybrid systems for remote work sites. USP&E is an EPC and O&M contractor, not a broker, with 150+ power projects in 45+ countries, 25,000 MW contracted since 2002 and 24+ years in the field. Our operations and maintenance teams support these systems in the field.
Offices: Colorado Springs (1755 Telstar Dr, Suite 300), Knoxville (800 S Gay St, Suite 700), London (162-168 Regent Street), Johannesburg (22 Kildoon Rd, Bryanston), Cape Town (31 Brickfield Road, Woodstock) and China (No. 1 Ningzhou Road, Wuxi). Regions: USA | AFRICA | UK | UAE | CHINA. ISO 9001 and ISO 45001 certified.
Motor and surge load questions
Can a solar trailer run a water pump?
Yes, if the inverter and battery can supply the pump’s starting current. A variable speed drive or soft starter often makes this possible on a smaller trailer.
How much surge does a motor need to start?
A direct-on-line induction motor typically draws five to seven times its full load current until it reaches speed.
What size inverter do I need for a 1.5 kW pump?
Started direct-on-line, it may need around 14 kVA for a moment. With a variable speed drive, a much smaller inverter can usually start it.
Why does my solar trailer shut down when a compressor starts?
The compressor’s inrush exceeds the inverter’s surge rating or the battery’s discharge limit, so the inverter or BMS protects itself.
Does battery charge level affect surge capacity?
Yes. A low state of charge or cold cells reduce the current the battery can deliver, so surge capacity falls.
Is a variable speed drive better than a soft starter?
For pumps and compressors a drive usually starts with lower current and allows speed control, but check harmonic compatibility with the inverter.
Check your motor loads
Send the nameplate data and duty cycle of the motors you need to run, and our engineers will check inverter, battery and starter options for your solar trailer.
Use the hybrid power enquiry form for a structured request, email info@uspeglobal.com with any site data you hold, or ring +27 10 822 2324 to speak to an engineer. For assist generators, see our diesel generator sets in stock.